LT4000M (module type DIO), PNP output, DC24V (host).For 3.8 inch models, connect the connector to the DIO interface. For connecting external I/O devices. (5 / set)7 inch widescreen display module installed on the senior panel adapter GP-2400, GP-3400 and GP-4400 series of holes.DIO model /NPN output type.
Display size: 5.7 inches.
Resolution: 320 x 240 pixels (QVGA).
LCD:TFT.
Color: 65536 color.
Ethernet interface: 1
PFXZLTEUALM3LT
Serial port: 1.
CANopen interface: 1.
USB (host):1.
USB (equipment):1.
Built in DIO input: 20 points.
Built in DIO output: 10 points.
Built in AIO input: No.
Built in AIO output: No.
Common DIO:2 point high speed counter (with synchronous output) pulse capture input.
Dedicated DIO:2 point pulse output, PWM output.
Expansion module EX module: none.
Expansion module CANopen module: 63 stations.
Controller memory size: EPROM 132KB FLASH (equivalent to 15000 steps (up to 60000 steps).
Flexible installation.
The control module can be installed on the DIN guide rail by using the split installation cable,
And the display module is installed in other locations.
Display module occupies a small space, even if the space is limited, but also can be flexible to install.
Compact size.
The volume is small but the display is fresh and bright, can create a rich and readable operation picture.
The control function of the whole and the digital I/O, analog I/O, analog temperature input and USB, serial port and Ethernet communication interface.
Integrated design.
Adopt integrative design, compact structure,
When the installation is only required to open a hole in the panel 22mm.
The display module or the control module can be easily replaced when the fault is eliminated. Applicable to GLC-2600/2500, the need for bus converter (PSL-CONV00).Display size: 5.7 inches.
Display type: STN pseudo color LCD.
Display color: 64 color.
Resolution: 320 x 240 pixels.
Input voltage: DC24V.
Control memory: EPROM 1MB FLASH.
Program area: 128KB.
Variable area: 32KB.
Interface: built-in DIO 32 points (16 point input /16 point output, type NPN) NETWORK +FLEX interface.
PFXZLTEUALM3LT Operation manual / Instructions / Catalog download link: